Battery power sets how quickly energy can move. Battery capacity sets how much can be held. Duration connects them, but it does not replace either input. A useful sizing study starts by reading that energy budget before looking at a financial rank.

Explore two modelled Network Map sizing and asset-curve examples reviewed on 7 November 2026. One changes battery size; the other applies a supplied capacity-retention curve.

Read Power And Capacity Together

The North depot sizing example compares a 1 kW / 2 kWh battery with a 2 kW / 4 kWh battery. Dividing nameplate energy by rated power gives 2 hours for each. The larger candidate doubles both power and capacity while keeping the same nameplate duration.

Same Duration, Different Scale. Example sizing candidates · 7 November 2026. 1 kW battery: 2 Nameplate capacity (kWh); 2 kW battery: 4 Nameplate capacity (kWh).
Example sizing candidates · 7 November 2026. Both candidates have 2-hour nameplate duration. Source: Network Map.

Explore Project Modelling

That means the comparison tests scale, not a longer-duration design. The energy available to a particular dispatch instruction also depends on starting charge, permitted state-of-charge bounds, conversion efficiency and any reserved capacity. Keep those controls visible beside the nameplate values.

A power limit can bind before energy is exhausted. An energy limit can bind even when converter power remains available. Reading both dimensions prevents a larger number in one column from being mistaken for a universally better operating envelope.

Use Financial Ranking With Explicit Cost Inputs

The saved fast-estimate comparison returned NPV of AUD 3,373.81 for the 1 kW / 2 kWh candidate and AUD 3,899.50 for the 2 kW / 4 kWh candidate. Reported IRRs were 41.51% and 46.13%, with discounted payback of 2.69 and 2.42 years respectively.

In this controlled comparison, fixed total capital cost stayed constant across the tested sizes. The result therefore shows the effect of the supplied size and dispatch assumptions on that fixed-cost basis. For an investment comparison, enter the actual equipment and installation cost for each candidate before adopting a design.

The fast estimate uses first-year operating physics and financial projections for later years. Save a chosen candidate as its own draft, retain the input basis and review its detailed energy result alongside its return metrics.

Track Capacity Through The Study Horizon

A separate equipment example starts with a 20 kW / 40 kWh battery. The supplied retention curve is 100% at age zero and 90% at age one. The completed two-year screening run applies 40 kWh in model year one and 36 kWh in model year two.

Apply The Supplied Capacity Curve. Separate 20 kW battery example · two-year horizon. Model year 1: 40 Applied capacity (kWh); Model year 2: 36 Applied capacity (kWh).
Separate 20 kW battery example · two-year horizon. Authored retention: 100% at age 0, then 90% at age 1. Source: Network Map.

This is an authored retention assumption, so its source belongs with the equipment version. It describes how the study changes available capacity at the year boundary. It should be read together with the power rating and the operating strategy, rather than treated as a new energy purchase or an extra revenue stream.

The same discipline applies when replacing equipment. Keep the cost of replacement, the equipment version and the physical assumptions aligned. A finance entry and a change to operating capacity are different parts of the project record.

Choose A Size For A Defined Job

  • State the job: shifting site energy, managing an operating limit or supporting a contracted service.
  • Check power, capacity and usable charge range before duration.
  • Compare candidates with explicit cost and retention assumptions.
  • Retain the selected case revision so the reported returns trace to the chosen equipment.

Start with DER Design, then use Dispatch Calendars And Sizing for bounded comparisons. The Asset Screening guide shows how to bind a capacity curve. Observed fleet values remain available separately in Battery Revenue Benchmarks.